Copper for gas is an area where the standards matter enormously and the differences between markets are significant. What is standard practice in the UK is not necessarily permitted in Germany. What is acceptable for natural gas may not be acceptable for LPG. Get this wrong and you have a safety hazard — potentially a serious one.
Here is the market-by-market picture. It is an overview for orientation — the installation standard in force at the site, and the gas network operator, always have the last word.
Copper for Gas in the UK
In the United Kingdom, copper tube to BS EN 1057 with appropriate fittings is a fully accepted material for internal natural gas and LPG installations. Domestic-size pipework (up to 35 mm) is installed to BS 6891; industrial and commercial pipework to IGEM/UP/2 (Installation pipework on industrial and commercial premises). The work itself is reserved for Gas Safe registered engineers.
Permitted connection types for copper gas pipework in the UK:
- Capillary fittings: soft-soldered with a lead-free solder to BS EN ISO 9453, or brazed. BS 6891 accepts both on low-pressure domestic pipework — this is the main difference from Germany and the USA, where soft solder is not allowed on gas.
- Compression fittings: Type A (with olive) to BS EN 1254-2, rated for gas service by their manufacturer — and only where the joint stays accessible.
- Press-fit fittings: Approved press-fit systems with appropriate gas-rated O-rings (HNBR for gas, not EPDM which is water-rated).
A soft-soldered joint loses its strength at a far lower temperature than a brazed one. That is the reason other countries exclude soft solder from gas pipework, and the reason UK practice keeps soft-soldered joints away from sources of heat and requires brazed or mechanical joints for higher pressures — follow the tables in BS 6891 and IGEM/UP/2 for the actual limits.
A press-fit fitting with an EPDM O-ring (standard for water) is not acceptable for gas. Gas-rated press-fit fittings use HNBR (hydrogenated nitrile butadiene rubber) O-rings, which are resistant to gas and gas odorants. The two types look identical — always verify O-ring specification before using press-fit on gas.
Copper for Gas in Germany and the EU
The picture is different in Germany. DVGW (Deutscher Verein des Gas- und Wasserfaches) rules govern gas installations: the installation code is DVGW G 600 (the DVGW-TRGI), the copper tube must meet DIN EN 1057 together with DVGW worksheet GW 392, and jointing follows worksheet GW 2. Copper gas pipework is brazed or pressed with fittings approved and marked for gas — soft soldering is not permitted, because a soft-soldered joint fails early in a fire. German practice uses steel and PE for buried and distribution pipework, with copper inside the building.
Across the EU, EN 1057 copper tube is generally approved for internal gas installations but the specific national annexes and utility requirements vary. Always check the local gas distributor network requirements for the installation region — network operators sometimes have requirements that go beyond the minimum standard.
Copper for Gas in the USA
In the USA, the National Fuel Gas Code (NFPA 54) and the International Fuel Gas Code accept copper tubing for natural gas and LP gas: Type K or L to ASTM B88, or tube to ASTM B280. Joints are brazed with a filler metal melting above 1,000 °F (538 °C), flared, or made with press-connect fittings listed to ANSI LC 4 / CSA 6.32 — soft solder is not accepted. Local codes and utilities may be stricter than the model codes, so check before specifying copper.
The exception is sour gas: NFPA 54 does not allow copper or copper-alloy tubing where the gas contains more than an average of 0.3 grains of hydrogen sulphide per 100 standard cubic feet (0.7 mg per 100 litres), because H₂S attacks copper directly. Where the supply exceeds that limit, steel or another listed material is used.
Tube Specification for Gas Service
| Market | Tube Standard | Grade | Temper |
|---|---|---|---|
| UK / EU | BS EN 1057 (Germany: plus DVGW GW 392) | Cu-DHP (CW024A) | R220 (annealed), R250 (half-hard) or R290 (hard) |
| USA | ASTM B88 or ASTM B280 | C12200 (DHP equivalent) | Type K or L only (NFPA 54) — Type M is not accepted for fuel gas |
| Australia / New Zealand | AS 1432 | Phosphorus-deoxidised copper | Tube type as permitted by AS/NZS 5601.1 for the operating pressure |
For exposed runs, half-hard (R250) or hard (R290) straight lengths are generally preferred over annealed (R220) coils — the stiffer tube sags less between supports and resists knocks better. Annealed tube is used where flexibility is needed, such as final connections to appliances.
Pressure Limits and Sizing
Domestic natural gas installations in the UK typically operate at 21 mbar (2.1 kPa) for the installation downstream of the meter. This is extremely low pressure compared to the pressure capability of copper tube and fittings — even a small compression fitting is rated well above this. The design limiting factor for gas pipework size is pressure drop along the run, not fitting pressure rating.
Higher-pressure gas installations (commercial, industrial, boosted systems) need tube wall thickness, fittings and jointing methods selected from the pressure tables of the installation standard — IGEM/UP/2 in the UK. Above 0.5 bar, UK installations also come under the Pressure Systems Safety Regulations 2000, which require a written scheme of examination.
Tightness Testing Before Commissioning
After installation, all gas pipework must be tightness tested before being put into service. In the UK, this follows the IGEM/UP/1 family of procedures (IGEM/UP/1B for domestic-size installations): new pipework is tested with air or an inert gas before any fuel gas is admitted, the pressure is held for a defined period, and any drop is assessed against the permitted limit. Existing installations are re-tested at operating pressure after any work. The engineer records the result before the system is purged and commissioned.
This is not optional, it is not a formality, and it applies to every gas installation including simple meter repositions. A gas leak in a building is a life safety issue. The tightness test exists precisely to find installation errors before gas is present to find them first.
Find our articles useful? ★ Add Brassland as a preferred source on Google to see our articles more often in your search results.
Frequently asked questions
Can copper be used for gas pipework?
Why is brazing used instead of soldering for gas copper?
What standards apply to copper gas fittings?
Sources & references
Gas-service references:
Last reviewed: September 2026. Standards and regulatory references are checked at each review.
Looking for Reliable Brass Fittings?
We machine brass, copper and aluminium parts to your drawing — ISO 9001, 14001 and 45001 certified, with an EN 10204 3.1 certificate on every shipment. Tell us what you need and we will get back to you within 24 hours on working days.
Request a Quote Browse ProductsRelated products, specifications & resources
Hand-picked links from the Brassland product catalogue and technical knowledge base — go directly to what was referenced in this article.
Request a quote › Contact engineering › Browse knowledge base ›